Gas Forced Air FAQ
Dyna-Glo RMC: FA-40, FA-50, FA-100, FA-150, and FA-300
Dyna-Glo Pro RMC: FA-40, FA-50, FA-100 and FA-150
Thermoheat RMC: FA-50 and FA-100
Trouble Possible Cause Corrective Action
Fan Does not turn when electrical connection is made
  1. No electric power to heater.
  2. Fan black contacts inside of heater housing.
  3. Fan blade(s) bent.
  4. Fan motor defective.
  1. Check current to electric outlet. If voltage is correct, check power cord and extension cord for cuts and breaks.
  2. Be sure that housing is not damanaged.
  3. Straighten blade(s) to match others.
  4. Replace motor.
Heater will not fire.
  1. No spark at ignitor.
  2. Improper spark gap.
  3. Bad electrode.
  1. Check ignitor wire. Re-attach or tighten if loose. Check Spark module. Replace if necessary.
  2. Set gap to 0.16" (0.08" for RMC-FA300)
  3. Replace Spark Plug.
Heater quits while running.
  1. Internal temperature too high causing limit switch to shut down operations.
  2. Damage Control Valve.
  3. Dust or debris build-up inside of heater.
  1. If the heater output is restricted, internal temperature becomes too high. Move heater away from any obstructions.
  2. Replace Control Valve.
  3. Clean inside of heater.